Enter the volumetric leak flow in m³/h or m³/s, or convert from a mass flow in g/s or kg/s using molar mass and the NPR 7910-1 molar volume of 25 m³/kmol. The calculation always uses m³/h and g/s.
m³/h ( m³/s)
a = value × 3600
a = a_m × (1/M) × 25 × 3.6
Installed ventilation must be at least the higher of the NPR 7910-1 VC and 4 air changes per hour.
m³/h
Governing value:
VC = a × (100 / LEL) × (100 / k). Air-change VC = room volume × 4. Installed ventilation ≥ max(VC, air-change VC).
Based on the Dutch NPR 7910-1 standard.