Leak flow rate

Enter the volumetric leak flow in m³/h or m³/s, or convert from a mass flow in g/s or kg/s using molar mass and the NPR 7910-1 molar volume of 25 m³/kmol. The calculation always uses m³/h and g/s.

Converted volumetric leak flow rate (a)

m³/h ( m³/s)

a = value × 3600

g/mol
Converted volumetric leak flow rate (a)

m³/h ( m³/s)

a = a_m × (1/M) × 25 × 3.6

LEL and safety factor

vol%

Room size

Installed ventilation must be at least the higher of the NPR 7910-1 VC and 4 air changes per hour.

Minimum Required installed ventilation

m³/h

Governing value:

NPR 7910-1 VC
m³/h
VC at 4 air changes/h
m³/h
Volumetric leak flow rate (a)
m³/h
Room volume
LEL
vol%
k

VC = a × (100 / LEL) × (100 / k). Air-change VC = room volume × 4. Installed ventilation ≥ max(VC, air-change VC).

NPR 7910-1 Mechanical ventilation calculation for secondary sources of release

Based on the Dutch NPR 7910-1 standard.